350

Liquidtight Flexible Metal Conduit (LFMC)

Flexible metal conduit sealed in a watertight plastic jacket — the wet-location connection for outdoor and washdown equipment.

Introduced
1978
Level
NEC (National)
Why this code exists
Safety incident
Current status
Active

Why this code exists

Bare FMC lets water into the wiring; the liquidtight jacket keeps moisture, oil and dust out where equipment sits outdoors or gets hosed down.

LFMC is flexible metal conduit wrapped in a sunlight- and liquid-resistant plastic jacket, terminated with sealing fittings. It gives you the flexibility of Greenfield plus a watertight seal, which is why it makes the final connection to rooftop HVAC units, outdoor motors, pumps and any equipment in wet or oily environments.

Like FMC, its ability to act as a ground path is limited by length and fitting listings, so a bonding conductor is commonly run inside. The liquidtight fittings must be the type listed for the conduit to actually maintain the seal — a mismatched connector defeats the whole purpose.

When it applies

Liquidtight flexible metal conduit is your flexible, watertight connection for the last stretch to equipment that moves, vibrates, or sits in wet conditions. Think rooftop condensers, outdoor motors, and washdown areas where you need flex to absorb vibration and a jacket that keeps water out of the raceway.

Common mistakes

In the field

On a rooftop unit I use LFMC with proper liquidtight fittings and always pull a separate equipment grounding conductor. The jacket handles the weather while the flex takes the vibration off the connections.

Field note
Every rooftop condenser I've ever hooked up got liquidtight for the last couple feet. The trick people botch is the fitting — you have to use the connector listed for that conduit and seat the O-ring, or water walks right past your 'watertight' jacket into the disconnect.
— Marcus · Journeyman · 18 yrs