Air-Conditioning & Refrigerating Equipment

Motor-compressor rules for AC and refrigeration — using nameplate values like RLA and MCA to size circuits and disconnects.

Introduced
1953
Level
NEC (National)
Why this code exists
Fire hazard
Current status
Active

Why this code exists

Hermetic compressor motors are sealed and rated differently from ordinary motors; this article adapts the motor rules to their special nameplate ratings.

Article 440 builds on Article 430 for the hermetic motor-compressors inside air conditioners, heat pumps and refrigeration equipment. Because these motors are sealed in the refrigerant system, they carry their own nameplate ratings — rated-load amps (RLA), minimum circuit ampacity (MCA) and maximum overcurrent protection (MOCP) — and the electrician sizes conductors and protection directly from those numbers.

The article requires a disconnecting means within sight of the equipment, addresses the combined load of the compressor plus fan motors, and coordinates with room air-conditioner and branch-circuit rules. For most field work, the golden rule is simple: follow the nameplate — MCA sets your wire, MOCP caps your breaker.

When it applies

Air-conditioning and refrigeration equipment run on hermetic motor-compressors, and Article 440 sizes their circuits from nameplate values rather than horsepower. You use figures like the rated-load amps and the minimum circuit ampacity to pick the conductors, and the maximum overcurrent protection to size the breaker or fuses and the disconnect.

Common mistakes

In the field

I size straight off the data plate: conductors to the MCA, protection at or below the max marked, and a disconnect within sight of the condenser. The nameplate is the law on these units, not the rule of thumb.

Field note
On HVAC gear you don't calculate from scratch like a bare motor — the manufacturer did the math for you. The MCA tells you the minimum wire, the MOCP tells you the biggest breaker or fuse you're allowed. Ignore the nameplate and slap on whatever breaker fit the wire, and you've just voided the listing and maybe cooked a compressor.
— Marcus · Journeyman · 18 yrs