Communications Circuits
Rules for telephone and data communications wiring — the twisted-pair and structured cabling that carries voice and network signals into and around a building.
Why this code exists
Phone and network lines run everywhere people are, and they can pick up lightning or cross a power line outside. Protectors and grounding at the entrance keep that energy from riding the wire to your hand.
Article 805 covers communications circuits — traditional telephone wiring and the twisted-pair data cabling (like Category structured cabling) that dominates modern buildings. It draws its common rules from Article 800 and adds the specifics for this circuit type: where a primary protector is required, entrance cable, and the listing types (CM, CMR, CMP, CMX) matched to plenum, riser, and general locations.
A big modern driver here is powered communications cable — Power over Ethernet. As PoE pushes more current down data cable to feed cameras, access points, and lights, the article added attention to conductor heating in large cable bundles, so data cable carrying real power doesn't cook itself in a tray. Between protection at the entrance and thermal limits in the bundle, 805 is where everyday network cabling meets electrical safety.
When it applies
Article 805 covers communications circuits, the telephone and data cabling, the twisted pair and structured wiring, that carries voice and network signals into and around a building. It sets how those cables enter, get protected against surges, get grounded, and stay separated from power wiring so the two systems do not interfere or create a hazard.
Common mistakes
- Skipping the primary protector and bonding at the point where the outside cable enters.
- Running communications cable in the same bundle or box as power without the required separation.
- Using cable not rated for a plenum or riser where the pathway demands it.
In the field
At the entrance I bond the communications ground back to the building's grounding electrode system, the same one the power service uses. Separate grounds sitting at different potentials are what let a surge find its way through the data gear.
PoE changed this article for me. When you're bundling fifty data cables feeding cameras and access points, that's real current, and a fat bundle in a hot ceiling can overheat. Follow the bundle-ampacity table, don't zip-tie two hundred cables into one bomb, and always land the entrance protector and bond it. Data cable earned its respect once it started carrying watts.
See full history
- 1975 — Communications circuit rules established in Chapter 8.
- 1993 — CM/CMR/CMP cable listing types formalized.
- 2017 — Bundle-ampacity limits added for Power over Ethernet.
- 2020 — Common rules moved to Article 800; 805 slimmed to circuit specifics.