Fire Pumps
Governs the power supply to fire pumps, deliberately favoring reliability and keeping the pump running over the usual overload protection, because losing the pump during a fire is worse than losing the motor.
Why this code exists
A fire pump must keep pushing water even if it destroys itself doing so, so its circuit is designed to run to failure rather than trip and leave the building without suppression.
Article 695 turns normal thinking upside down. For any ordinary motor you protect the motor from overload; for a fire pump you protect the mission. The supply conductors and overcurrent are sized and set so the pump keeps running under overload conditions, accepting that the motor may burn up rather than shutting down while the building is on fire. It also demands a reliable source, protected wiring routing, and often an alternate supply.
This one takes discipline to build correctly because every instinct I have says protect the equipment, and here the code says protect the water. I run the fire-pump feeder to survive, keep it separated and protected from the fire itself, and set the overcurrent to let the pump run to destruction if that is what it takes to keep the sprinklers wet.
When it applies
Fire pumps are wired to keep running, even at the cost of the motor. Article 695 deliberately trades normal overload protection for reliability, because a pump that trips offline during a fire is far more dangerous than a motor that burns up while still moving water. The supply is arranged so the pump keeps pushing as long as it possibly can.
Common mistakes
- Applying ordinary motor overload protection that could shut the pump down mid-fire.
- Feeding the pump from a supply that is not arranged for the required reliability and separation.
- Undersizing conductors that must carry locked-rotor current without opening.
In the field
On a fire-pump feeder I size for locked-rotor and route it for maximum survivability, keeping it independent and protected. The mindset flips here: we protect the building's water supply, not the motor.
Everything in me says protect the motor, and this article says protect the water. I set the fire-pump circuit to run the motor to destruction if it must, and I route the feeder to survive the fire, because a dead pump during a fire is the real failure.
See full history
- 1996 — Fire pump article consolidated into a dedicated set of rules.
- 2011 — Source reliability and circuit protection provisions strengthened.
Related codes
Open interactive version →Codex is an independent educational reference. Not the National Electrical Code® and not affiliated with the NFPA. Always verify against the adopted code and your AHJ. · Privacy