Outlet, Device, Pull & Junction Boxes and Conduit Bodies

How to size boxes for the conductors and devices inside them, how to support them, and where junctions must stay accessible.

Introduced
1937
Level
NEC (National)
Why this code exists
Safety incident
Current status
Active

Why this code exists

Overfilled boxes trap heat and damage insulation, and buried junctions can't be inspected when they fail; the box-fill and accessibility rules address both.

Article 314 sizes the humble box. Every conductor, device, clamp and equipment-grounding conductor claims a volume allowance, and the total can't exceed the box's cubic-inch rating. The point is heat: a stuffed box can't shed the warmth of its splices, and the crowding nicks insulation during makeup.

The article also demands that junction and pull boxes stay accessible — no burying a splice behind drywall — and sets how boxes must be supported and how far they can be set back from a finished surface. For large pull boxes it gives distance formulas so conductors aren't bent tighter than they can stand.

When it applies

Article 314 governs sizing and supporting your boxes and conduit bodies. Every conductor, device, clamp, and equipment ground inside counts toward box fill, and any splice has to stay accessible behind a cover you can reach later.

Common mistakes

In the field

I opened a switch box in a remodel that was so packed I could barely fold the wires back in. Someone ignored the fill math and the connections were stressed and warm. I stepped up to a deeper box and everything relaxed. Do the fill calculation before you rough in, and never plaster over a junction. The next electrician, maybe you, has to get back into it.

Field note
Box fill is the calculation homeowners never think about and I never skip. A deep old-work box costs a couple dollars more and saves you from folding six conductors and a dimmer into a shallow can that was never rated for it. If you can't count the volume in your head, it's already too full.
— Priya · Journeyman · 12 yrs