Communications Circuits — Grounding and Bonding
Communications cables entering a building need a bonded protector and their shields grounded to the building's grounding system to safely handle surges.
Why this code exists
Outside cables can pick up lightning and power-line surges; bonding them to the same ground as the electrical service keeps dangerous voltage differences from developing.
The key is bonding to a single point: the communications ground ties to the same electrode system as the power service. If the phone or data ground and the power ground are at different potentials, a surge finds its way through your equipment.
Chapter 8 stands mostly on its own, but this grounding rule is where it shakes hands with the rest of the Code. One building, one ground reference.
When it applies
This applies where communications cabling — phone, some broadband and similar circuits — enters a building. A listed primary protector goes at the entrance and its bonding conductor and any cable shields tie back to the building's grounding electrode system so a surge has a low-impedance path to earth instead of through the equipment.
Common mistakes
- Bonding the protector to a random ground rod separate from the power grounding electrode, creating a difference in potential.
- Running an overly long, sharply bent bonding conductor that fights fast surge currents.
- Leaving the shield floating and hoping the equipment survives the next lightning event.
In the field
I always bond the comms protector to the same grounding electrode system as the electrical service, short and straight. When everything shares one ground reference, a surge lifts the whole system together instead of arcing across your gear looking for a path.
The rule I preach on every comms install is one building, one ground. When the data ground and the power ground sit at different potentials, the first storm sends the difference straight through the customer's router.
See full history
- 1975 — Communications grounding requirements consolidated.
- 2017 — Chapter 8 grounding language unified across communications articles.