376.22

Metal Wireways — Fill and Ampacity

Metal wireways are trough-like raceways with removable covers; the conductors inside are limited to 20 percent fill and are subject to derating when many are bundled.

Introduced
1953
Level
NEC (National)
Why this code exists
Fire hazard
Current status
Active

Why this code exists

A wireway packed full traps heat and leaves no room to work, so the fill and derating rules keep the conductors from overheating.

Wireways make a great gutter for terminating and distributing lots of circuits at a panel. Keep the conductors to 20 percent of the cross-section, and once you pass 30 current-carrying conductors the derating kicks in.

The removable cover tempts people to treat it as unlimited space. It is not — the same heat physics apply as in any raceway.

When it applies

Metal wireways serve as accessible troughs for grouping many conductors with removable covers for easy changes. Conductor cross-section is limited to twenty percent of the interior, and once more than a set number of current-carrying conductors ride together, ampacity derating applies.

Common mistakes

In the field

On a plant control-room job I inherited a wireway stuffed near solid with conductors. The thermal load was pushing insulation past rating and the terminations discolored. I re-engineered the fill, split conductors across two wireways, and applied the correct derating factor. The trough runs cool now. Wireways are generous, but the fill and derating math still governs the heat.

Field note
I use wireways as gutters above motor control centers, but I count conductors like a hawk. Just because the cover pops off does not mean the heat has anywhere to go.
— Marcus · Journeyman · 18 yrs