Service-Entrance Cable (Types SE & USE)
Heavy cable that carries service or feeder power from the meter to the panel, and its underground cousin USE.
Why this code exists
Service conductors carry the full load of a building; the article ensures the cable and its uses match that demand and the environment it passes through.
Type SE cable brings power from the meter into the service equipment, and it's also widely used for feeders and large appliance circuits like ranges and dryers. USE (underground service entrance) is the direct-burial version with moisture-resistant insulation for the run from a transformer or pole.
A key caution lives in the interior use of SE cable: when used as an interior branch circuit or feeder in an unprotected space, its conductor ampacity must be figured on the 60-degree column, because the cable can be run through thermal insulation where it can't shed heat. USE alone lacks the flame rating to come indoors as premises wiring.
When it applies
Service-entrance cable, Type SE, carries the heavy conductors from the meter to the main panel and sometimes feeds subpanels. Its underground relative, Type USE, is rated for direct burial. You will see SE on the outside of a house running from the weatherhead down to the meter and into the service equipment.
Common mistakes
- Using indoor SE where the run is exposed to conditions calling for the underground-rated USE.
- Relying on the uninsulated bare conductor as a neutral in an interior feeder application where that is no longer permitted.
- Failing to protect the cable from physical damage where it comes down a wall within reach.
In the field
On feeder runs inside a dwelling I treat that concentric bare conductor carefully. Rules tightened on using it as a neutral downstream, and I size and run a proper four-wire feeder rather than lean on old habits.
The gotcha that trips people is running SE cable indoors for a feeder and sizing it off the 90 column like it's THHN. Once that cable's buried in attic insulation it can't breathe, so the Code makes you use 60 degrees. Size it right up front and you won't be re-pulling a feeder that runs hot.
See full history
- 1941 — Recognized for service-entrance conductors.
- 2015 — Clarified 60°C ampacity for interior SE runs in insulation.